Shrubs should be trimmed, dogs restricted, and pathways should be clear for safe access to metering equipment. Meters shall not be enclosed or put in the rear of buildings or in a location that is fenced. Pathways need to be a minimum of 2 feet in width and if there is a walkway over a ditch that is wider than 6 feet, a structurally sound handrail is required. Clear space in front of the meter equipment shall be 36″ deep, as wide as the equipment or 36 inches (whichever is greater), and as high as the top of the equipment or at least 6 feet and 6 inches high.
Meters shall be readily removable (not plastered or built-in), and not recessed behind the exterior wall surface. Any meter that is installed in an alley or driveway must be flush mounted on the wall and protected adequately to prevent damage from vehicular traffic. In the event of loss or damage to District property arising from neglect, carelessness, or misuse, the cost of necessary repairs or replacement will be billed to the Customer.