Section 7: Connection of Motors to District Facilities

A. General

Approval of the District is required before installation of any single-phase motor exceeding 5 horsepower or combination of single or poly-phase motors exceeding 15 horsepower.

B. Large Motors

Starting of any motor shall not produce more than a 2% dip in primary voltage, or more than a 3% dip in service voltage of any other customer. Larger voltage dips shall be mitigated at the expense of the motor owning customer.